| AC-1 | IEC 60947-4-1 | Non-inductive or slightly inductive loads: resistance furnaces, heaters |
| AC-2 | IEC 60947-4-1 | Slip-ring motors: starting, switching off |
| AC-3 | IEC 60947-4-1 | Squirrel-cage motors: starting, switching off running motors |
| AC-3e | IEC 60947-4-1 | High-efficiency squirrel-cage motors with a higher locked-rotor current: starting, switching off running motors |
| AC-4 | IEC 60947-4-1 | Squirrel-cage motors: starting, plugging, inching |
| AC-5a | IEC 60947-4-1 | Switching of discharge lamps |
| AC-5b | IEC 60947-4-1 | Switching of incandescent lamps |
| AC-6a | IEC 60947-4-1 | Switching of transformers |
| AC-6b | IEC 60947-4-1 | Switching of capacitor banks |
| AC-8a | IEC 60947-4-1 | Hermetic refrigerant compressor motors, overload releases reset by hand |
| AC-8b | IEC 60947-4-1 | Hermetic refrigerant compressor motors, overload releases reset automatically |
| DC-1 | IEC 60947-4-1 | Non-inductive or slightly inductive loads: resistance furnaces |
| DC-3 | IEC 60947-4-1 | Shunt motors: starting, plugging, inching, dynamic braking |
| DC-5 | IEC 60947-4-1 | Series motors: starting, plugging, inching, dynamic braking |
| DC-6 | IEC 60947-4-1 | Switching of incandescent lamps |
| AC-12 | IEC 60947-5-1 | Control of resistive loads and solid-state loads with opto-coupler isolation |
| AC-13 | IEC 60947-5-1 | Control of solid-state loads with transformer isolation |
| AC-14 | IEC 60947-5-1 | Control of small electromagnetic loads, up to 72 VA |
| AC-15 | IEC 60947-5-1 | Control of AC electromagnetic loads over 72 VA |
| DC-12 | IEC 60947-5-1 | Control of resistive loads and solid-state loads with opto-coupler isolation |
| DC-13 | IEC 60947-5-1 | Control of DC electromagnets |
| DC-14 | IEC 60947-5-1 | Control of DC electromagnetic loads with economy resistors in the circuit |
| AC-20 | IEC 60947-3 | Connecting and disconnecting under no-load conditions (switch-disconnectors) |
| AC-21 | IEC 60947-3 | Switching of resistive loads, including moderate overloads (switch-disconnectors) |
| AC-22 | IEC 60947-3 | Switching of mixed resistive and inductive loads, including moderate overloads (switch-disconnectors) |
| AC-23 | IEC 60947-3 | Switching of motor loads or other highly inductive loads (switch-disconnectors) |