How the marking is built
Ex, letters, group, class, level.
01Types of protection
Letters after Ex: d flameproof enclosure, e increased safety, i intrinsic safety, p pressurised enclosure, m encapsulation, o liquid immersion, q powder filling, n type n, t protection by enclosure for dust. A trailing a, b or c is the level: ia, db, ec.
02Group
IIA, IIB and IIC are gas groups, IIC the most demanding (hydrogen, acetylene); IIC equipment also meets IIB and IIA. IIIA, IIIB and IIIC are dust groups: combustible flyings, non-conductive and conductive dust. Group I is mining.
03Class and level
T1 to T6 cap the hottest surface, from 450 °C down to 85 °C; dust equipment marks the temperature itself, as T85 °C. The level Ga, Gb or Gc suits zone 0, 1 or 2; Da, Db and Dc zones 20, 21 and 22.
Temperature classes and the hottest surface each allows
| Class | Surface, at most | Also meets |
| T1 | 450 °C | — |
| T2 | 300 °C | T1 |
| T3 | 200 °C | T1, T2 |
| T4 | 135 °C | T1, T2, T3 |
| T5 | 100 °C | T1, T2, T3, T4 |
| T6 | 85 °C | T1, T2, T3, T4, T5 |
A zone also takes equipment of a stricter level: zone 1 takes Gb or Ga, zone 2 Gc, Gb or Ga. In the ATEX form, II 2G is equipment group II, category 2, gas; categories 1, 2 and 3 match zones 0, 1 and 2.
Sources
Types of protection and levels: Heating & Process ("Explosion protected equipment marking"), the R. STAHL marking guide and Wikipedia ("Electrical equipment in hazardous areas"); levels, zones and ATEX categories: BARTEC Academy and Wikipedia; groups and temperature classes: Wikipedia and Heating & Process; square brackets: HSA Ireland and Heating & Process; X and U: IECEx decision sheets, Heating & Process and Cortem Group; the normal ambient range: IEC 60079-0 as summarised by its publishers, and FM Approvals.