How is the heat loss of an insulated pipe worked out?
As two thermal resistances in series, per metre of pipe. The insulation layer: ln(r2 / r1) / (2 pi k), with r1 half the outside diameter of the pipe, r2 = r1 + the insulation thickness and k the conductivity of the insulation. The outer surface: 1 / (2 pi r2 h), with h the surface coefficient. The loss is q = (Tf - Ta) divided by the sum of the two. A steam pipe of 60.3 mm with 50 mm of insulation, k 0.04 W/(m K), h 10 W/(m2 K), steam at 180 °C and air at 35 °C: ln(80.15 / 30.15) / (2 pi x 0.04) = 3.890 m K/W and 1 / (2 pi x 0.08015 x 10) = 0.1986 m K/W, so q = 145 / 4.089 = 35.5 W/m, or 709 W over 20 m.
Why are the pipe wall and the inside film left out?
Because with insulation they are usually small: a steel wall and the film of the fluid inside each add a small fraction of the resistance of the insulation layer. The calculator takes the inner face of the insulation at the fluid temperature and says so with the result. Leaving them out can only make the loss come out higher, never lower, since each resistance left out would reduce it; the bare pipe figure is an upper estimate for the same reason.
Which figures does the calculator need, and where do k and h come from?
The outside diameter of the pipe and the insulation thickness in mm; the fluid and the air temperatures in °C (K and °F are read too); the conductivity k of the insulation in W/(m K) and the surface coefficient h in W/(m2 K); and, if wanted, the length in m, the operating hours per year, a price per MWh and the boiler efficiency. The calculator holds no default k or h and does not assume one: k comes from the data sheet of the insulation fitted, and h is the figure for the outer surface and the air around it, convection and radiation together. A line without k or h is answered with a request for the missing figure.
How does the bare pipe compare, and can insulation raise the loss?
A bare pipe loses q = h pi D (Tf - Ta) per metre: the same 60.3 mm pipe at 180 °C in air at 35 °C with h 10 loses 274.7 W/m, so 50 mm of insulation cuts the loss by 87.1 %. Without a separate bare surface h the comparison uses the same h; a bare surface is hotter and gives off more by radiation, so enter bare h for a closer figure. Insulation can raise the loss only while its outer radius is below k / h, the critical radius: with k 0.04 and h 10 that is a radius of 4 mm, and the calculator says so whenever the insulation entered is that thin.
How are the energy per year and the fuel cost worked out?
As plain arithmetic. The energy per year in MWh is the loss in W times the operating hours per year, divided by 1 000 000. The fuel burnt for it is that energy divided by the boiler efficiency, and the cost is the fuel energy times the price per MWh. A thermal oil line of 114.3 mm at 250 °C with 80 mm of insulation, k 0.045 W/(m K), h 9 W/(m2 K) and air at 40 °C loses 65.1 W/m; over 8000 h that is 0.521 MWh per metre per year; with a boiler efficiency of 85 % that is 0.613 MWh of fuel, and at 60 per MWh, 36.77 per metre per year. Bare, the same metre would cost 383.25.
Does the calculator check the surface temperature against a limit?
No. It gives the outer surface temperature, Ts = Ta + q / (2 pi r2 h): 42.0 °C for the steam pipe above. Surface temperature limits follow SOLAS II-2 and the rules for the space, and the calculator puts no limit figure next to the result.