How is the air flow for a cooling or heating load worked out?
From the sensible heat of the air: Q = m cp delta T with the mass flow m = density x V, so Q in kW = density x cp x V x delta T with V in m3/s. For the air flow, V = Q / (density x cp x delta T). A cooling load of 12 kW with a temperature difference of 10 K between the room and the supply air: V = 12 / (1.2 x 1.006 x 10) = 0.9940 m3/s, or 3578 m3/h. The same relation gives the load for an air flow and a temperature difference, or the difference for a load and an air flow. It is sensible heat only: the latent heat of the moisture taken out of the air is not included.
Which air density and specific heat does the calculator use?
Unless other values are entered, 1.2 kg/m3, the standard air density at 20 °C and 1013 mbar, and 1.006 kJ/(kg K) for the specific heat of air; together 1.2 x 1.006 = 1.2072 kJ/(m3 K), so 1 m3/s of air warmed or cooled by 1 K takes up or gives off about 1.21 kW. When the design works with other values, enter them in the line (density 1.16 kg/m3 cp 1.005) or in the fields, and the working uses them.
How are the air changes per hour worked out?
The air changes per hour are the air flow in m3/h divided by the room volume in m3: 1500 m3/h through a room of 4 x 3 x 2.5 m, 30 m3, is 50 air changes per hour. With the air changes entered, the calculator gives the air flow instead: 10 per hour in 30 m3 is 300 m3/h. It gives no recommended rates: take them from the ship’s air handling design; the applicable standard sets the design conditions and the basis of calculation for the air conditioning and ventilation of accommodation spaces.
How is a duct sized for an air velocity?
The duct area is the air flow divided by the velocity, A = V / v. The round duct diameter is then the square root of 4 A / pi, and a square duct has the side the square root of A; with one side of a rectangular duct entered, the other side is A divided by it. For 3600 m3/h at 8 m/s: V = 1 m3/s, A = 0.125 m2, a round duct of 399 mm or a square duct of 354 x 354 mm. In an existing duct the calculator gives the velocity, V / A. It gives no recommended velocities: take them from the design of the system.
What is the equivalent diameter of a rectangular duct?
The round duct with the same friction loss per metre at the same air flow, by the Huebscher relation De = 1.30 (a b)^0.625 / (a + b)^0.25, in any one unit. For a 400 x 300 mm duct, De = 378 mm. It is not the duct of the same area: the round duct of 378 mm has 0.1120 m2 against 0.12 m2, so at 2000 m3/h the air runs at 4.96 m/s in it and at 4.63 m/s in the rectangular duct.
Which inputs and units does the calculator take?
Air flows in m3/h, m3/min, m3/s, l/s and cfm (1 cfm = 1.699 m3/h); loads in kW, W, kcal/h (1 kcal/h = 1.163 W) and BTU/h (1 BTU/h = 0.2931 W); the temperature difference in K, or the supply and room temperatures in °C, °F or K; the room as length x width x height in m, or its volume in m3, with the air changes per hour; duct sizes in mm, cm or m, a round diameter, a x b or one side; the velocity in m/s or ft/min; and, if wanted, the air density in kg/m3 and the specific heat in kJ/(kg K).