How is the heating temperature for a target viscosity worked out?
In three steps on the ASTM D341 relation, log10(log10(v + 0.7)) = A - B log10(T), with T in kelvin. First Z = log10(log10(v + 0.7)) at each of the two points. Then B = (Z1 - Z2) / (log10 T2 - log10 T1) and A = Z1 + B log10 T1. Last, for the target viscosity, log10 T = (A - Z) / B. For 380 mm2/s at 50 °C and 35 mm2/s at 100 °C: Z1 = 0.411718, Z2 = 0.191079, B = 3.5314 and A = 9.2734; a target of 13 mm2/s gives T = 407.6 K, that is 134.4 °C.
Why does the calculator need two points?
Because the line has two constants, A and B, and each fuel has its own slope B. One viscosity, such as 380 mm2/s at 50 °C, fixes a point but not the slope, and the calculator does not assume one: with one point only it says that a second measured viscosity at another temperature is needed, such as a viscosity at 100 °C from a fuel analysis report.
Which injection viscosity should I enter?
The injection viscosity the engine maker specifies for the engine. The calculator gives no injection viscosity and no heating temperature of its own: it gives the temperature at which the fuel, on the line through your two points, reaches the viscosity entered.
Can the line be used beyond the two points?
The line continues beyond them, and the calculator gives the figure, but it marks it as outside the two points: it is an extrapolation along the line, not a measurement. A measured viscosity nearer that temperature checks it. The table marks each row beyond the points in the same way.
What about viscosities below 2 mm2/s?
The calculator uses the plain form, with 0.7 added to the viscosity, from 2.0 mm2/s up. Below about 2 mm2/s ASTM D341 adds exponential terms to that 0.7, and the calculator does not apply them: a point, a target or a table row below 2.0 mm2/s is named as outside its range instead of given.
Which inputs, units and range does the calculator take?
Kinematic viscosities in mm2/s or cSt, which are the same, from 2.0 to 100 000 mm2/s; temperatures in °C, and also in K or °F, from -50 to 300 °C. Two points, each a viscosity with its temperature, and a target viscosity, a temperature to check or a table range. A dynamic viscosity in mPa s or cP, and Saybolt, Redwood or Engler figures, are not converted.