How is the boiler blowdown worked out?
From a mass balance. The dissolved solids come in with the feed water and leave only with the blowdown, because the steam carries next to none of them, so F x Cf = B x Cb, and the feed F is the steam S plus the blowdown B. The blowdown is B/F = Cf / Cb of the feed and B/S = Cf / (Cb - Cf) of the steam. Feed water at 20 ppm with a limit of 2000 ppm entered: B/F = 20 / 2000 = 1.00 % of the feed and B/S = 20 / 1980 = 1.01 % of the steam. At 3 t/h of steam the blowdown is 3000 x 20 / 1980 = 30.3 kg/h, and the feed is 3030 kg/h.
What are the cycles of concentration?
How many times the boiler water is more concentrated than the feed water: Cb / Cf, which equals F / B, the inverse of the blowdown as a share of the feed. At 20 ppm in the feed and 2000 ppm in the boiler water the cycles are 100, and the blowdown is 1/100 of the feed. The cycles can be measured by the ratio of the TDS, of the chloride or of the conductivity of the boiler water and the feed water.
What boiler water limit should be entered?
The one given for this boiler. Boiler water limits for TDS, chloride and alkalinity are set by the boiler maker and the water treatment supplier. The calculator prints no limit figure and does not assume one: without a limit it asks for it. Enter the limit for the same quantity as the feed water figure: TDS with TDS, chloride with chloride, conductivity with conductivity.
Can the calculator work with conductivity?
Yes. With the feed water and the limit both in uS/cm the blowdown comes straight from the ratio of the conductivities. With one figure in uS/cm and the other in ppm or mg/l, a factor from conductivity to TDS is needed (TDS = factor x conductivity), and the calculator asks for it instead of assuming one. Two steam engineering references give 0.7 ppm per uS/cm for a neutralised boiler water sample at 25 °C; the factor depends on the water, so take it from the meter or the water treatment supplier.
What boiler water does a given blowdown give?
Enter the blowdown and the feed water: the boiler water reaches Cb = Cf / (B/F). A blowdown of 2 % of the feed with feed water at 25 ppm gives 25 / 0.02 = 1250 ppm, 50 cycles of concentration, and 2 / 98 = 2.04 % of the steam. A blowdown as a per cent of the steam (2 % of steam), as cycles (cycles 50) or as a rate with the steam rate (blowdown 30 kg/h, steam 3 t/h) is read too. With a limit entered as well, the calculator says whether the boiler water stays within it.
Which inputs and units does the calculator take?
The feed water and the boiler water limit in ppm, mg/l (taken as equal to ppm for boiler and feed water) or uS/cm (mS/cm too), as TDS, chloride or conductivity; the steam rate in kg/h, t/h or kg/s if wanted; a blowdown in per cent, as cycles or as a rate for the reverse; a factor from conductivity to TDS when the units are mixed. A boiler pressure or a water temperature in the line is read and named as not used: the mass balance does not depend on them, and the heat lost in the blowdown is not worked out here.