How is the engine room ventilation air worked out?
In three steps. The combustion air: qc = m / rho, the air consumption of the engines and boilers divided by the air density 1.13 kg/m3; 28 kg/s gives 24.78 m3/s, or 89 204 m3/h. The air to remove the heat: qh = phi / (rho x c x dT); 350 kW with c = 1.01 kJ/(kg K) and a rise of 12.5 K gives 350 / 14.27 = 24.53 m3/s, or 88 320 m3/h. The total, the greater of qc + qh and 1.5 x qc: 49.31 m3/s against 37.17 m3/s, so 49.31 m3/s, or 177 524 m3/h. Shared by 4 fans, each moves 44 381 m3/h.
When does 1.5 x qc set the total?
When the air to remove the heat is less than half the combustion air: qc + qh is then below 1.5 x qc, and the total is 1.5 x qc. With 28 kg/s of combustion air (24.78 m3/s) and 100 kW of heat emission (7.01 m3/s), qc + qh = 31.79 m3/s, but 1.5 x qc = 37.17 m3/s, so the total is 37.17 m3/s, or 133 805 m3/h. The calculator shows which of the two sets the total.
Which temperature rise does the calculator take?
12.5 K, the design figure of the method for the rise of the air through the engine room, unless you enter another, such as delta T 10 K. A smaller rise needs more air: 350 kW at 10 K needs 350 / (1.13 x 1.01 x 10) = 30.67 m3/s, against 24.53 m3/s at 12.5 K. A rise above 12.5 K is worked out too, with a note that the method takes 12.5 K at most.
Where do the heat emission and the combustion air come from?
The engine maker’s project guide gives the air consumption and heat emission for each unit, and the boiler and generator data give theirs. The calculator has no figures of its own: add up the heat emission of the engines, generators, boilers and the other equipment in the room you have figures for, and the combustion air of the engines and boilers that take their air from the room. A power in kW is not a heat emission, and the calculator says so when a kW figure stands next to a power word.
How is the capacity of each fan found?
The fans share the total air: with 4 fans and 177 524 m3/h in all, each moves 44 381 m3/h, or 12.33 m3/s. The calculator does not choose reserve fans or a fan pressure; those follow your specification and the duct design. Fans already chosen can be checked: 4 x 45000 m3/h in the line, with the heat emission and the combustion air, is set against the total, and 180 000 m3/h is 101 % of 177 524 m3/h.
Which inputs and units does the calculator take?
The heat emission in kW or MW, one figure or several that are added up; the combustion air in kg/s, kg/h, t/h, m3/s, m3/h or m3/min, one figure or several, such as the engines and a boiler; the temperature rise in K, 12.5 K unless entered; the number of fans; and the fans already chosen, as 4 x 45000 m3/h, to check them against the total. A flow in m3 is turned into kg/s with the air density 1.13 kg/m3. The heat removal air is the gross figure: ISO 8861 itself takes a share of the combustion air off it, which the calculator does not do.