What does Dyn11 mean?
D: the HV winding is connected in delta. y: the LV winding is connected in star. n: the LV neutral is brought out to a terminal. 11: the clock number; the LV lags the HV by 11 x 30° = 330°, which is the same as leading it by 30°. The ratings of the transformer are not in the symbol: they are on the nameplate.
How is the clock number read?
Put the HV vector at 12 o’clock, the 0 of the clock face. The vector of the other winding points at the hour of its clock number, and each hour is 30° of lag. 0 is in phase, 1 is 30° behind, 6 is 180° (opposite) and 11 is 330° behind, that is, 30° ahead. The figures run from 0 to 11.
Why does the reader refuse Yy1 or Dd11?
Two windings of the same connection, star and star or delta and delta, give only even clock numbers (0, 2, 4, 6, 8, 10); a star and a delta give only odd ones (1, 3, 5, 7, 9, 11). Yy1, Dd11 or Dy0 on a document usually means a letter or a figure was copied wrongly: check the nameplate. Zigzag windings are not checked this way here.
What do YNyn0d5 and YNa0d11 mean?
The windings are listed in descending order of rated voltage, each after the HV with its own clock number. YNyn0d5: a star HV winding with the neutral brought out, a star intermediate winding with its neutral, in phase, and a delta LV winding lagging by 150°. In YNa0d11 the a marks a winding auto-connected with the HV winding (an autotransformer), in phase, and the delta winding lags by 330°.
Does the reader take the Russian writing?
Yes. The Russian standard GOST 11677 divides the windings by /, the HV first, and the group figure after a hyphen: delta and star with the neutral, group 11, is the same as Dyn11. Typed with Cyrillic letters (de, u, en) or with a Greek delta, the line is read the same way; the writing Y0 for the neutral and 12 for group 0 is read too.
Can Dyn11 and Dyn1 run in parallel?
Not as they are: the phase displacement is 330° for one and 30° for the other. Equal phase displacement is one condition for parallel operation; the voltage ratio and the impedance must match too. The makers’ data and the class rules govern, and IEC 60076-8 covers the parallel operation of transformers.